Industrial Systems Maintenance – electrical fault stand live view

The stand page shows the induction machine's phase voltages and currents in real time: waveforms, RMS values, the phasor diagram and the symmetrical components. It is view only: the faults are introduced by the instructor. Write down the values for each situation so you can determine which fault the machine has.

Watch the stand Works only in the lab, on the TP-Link_F996 Wi-Fi network.
Laboratory work

Electrical fault diagnosis of the induction machine

For each situation on the stand, record:

  • the voltages U1, U2, U3 and the currents I1, I2, I3 (RMS);
  • the residual current i1 + i2 + i3;
  • cos φ on each phase and the current unbalance factor KI.

Compare with normal operation and identify the fault: missing phase, insulation fault, additional resistance on one phase or short-circuited turns. Also state the affected phase.